Portable evaporative coolers that roll to the heat
Models from 6,000 to 20,000 CFM (larger by special order), with temperature drops up to 35°F. HV series units also install as suspension-mount or through-the-wall systems.
Pick the airflow, we'll handle the rest
Jobsite, space cooling, and extreme-duty ducted cooling. Click a model for full specifications.
Contractor Plus
Jobsite · 6,000 CFM

Built to travel: 6,000 CFM on 115 V, a narrow transport mode that converts to cooling in seconds, and a blower that runs on its own. For contractors, crews, and race, sports, and rescue teams.
| Fan | Detachable high-output aluminum fan |
|---|---|
| Airflow | 6,000 CFM · 5,000 CFM with 20′ duct |
| Temperature drop | Up to 35°F |
| Power | 115 V single phase · 12 A |
| Cooling mode | 47″ H × 39″ W × 42½″ D |
| Transport mode | 47″ H × 28½″ W × 57″ D |
| Dry weight | 195 lbs |
| Build | Aluminum chassis, pneumatic tires, stainless steel wet section, sump pump-down connection, washable aluminum pre-filters |
| Options | Flexible discharge duct |
HV 36-9
Space Cooling · 9,000 CFM

The starting point for open-area cooling — 9,000 CFM on a half-horsepower fan motor. Shops, single bays, and work areas one unit can cover.
| Fan | 36″ belt drive, four-blade |
|---|---|
| Airflow | 9,000 CFM |
| Motor | 0.5 HP fan, fractional pump |
| Power | 115/230 V single phase · 8.2/4.1 A |
| Dimensions | 54″ H × 48″ W × 40″ D |
| Dry weight | 300 lbs |
HV 48-15
Space Cooling · 15,000 CFM

Same job as the HV 36-9 with two-thirds more air — 15,000 CFM for larger floors, or where one unit has to reach past a single bay.
| Fan | 48″ belt drive, four-blade |
|---|---|
| Airflow | 15,000 CFM |
| Motor | 1.0 HP fan, fractional pump |
| Power | 115/230 V single phase · 12.0/6.0 A |
| Dimensions | 67″ H × 60″ W × 40″ D |
| Dry weight | 350 lbs |
HV 50-20
Flagship · 20,000 CFM

The highest-capacity portable evaporative cooler on the market — more coverage from a single unit than anything else you can roll through a door.
| Fan | 50″ belt drive, cast aluminum three-blade |
|---|---|
| Airflow | 20,000 CFM |
| Motor | 1.0 HP fan, fractional pump |
| Power | 115/230 V single phase · 13.4/6.7 A |
| Dimensions | 80″ H × 72″ W × 40″ D |
| Dry weight | 525 lbs |
HVTA-30 “The Boss”
Extreme Duty · 15,000 CFM

A high-pressure tube axial blower pushes conditioned air up to 100 feet through 30″ flex duct (or two 18″ ducts). Built for smelters, foundries, mines, power plants, and hot confined work areas.
| Blower | 30″ six-blade tube axial, belt drive |
|---|---|
| Airflow | 15,000 CFM @ 0.5″ static pressure |
| Motor | 5.0 HP fan, fractional pump |
| Power | 230/460 V three phase · 13.0/6.5 A |
| Dimensions | 66″ H × 60″ W × 48″ D |
| Dry weight | 375 lbs |
Standard across the line: stainless steel wet sections with easy water-system access, adjustable water flow, 12″ rigid media, digital output-air thermometers, GFCI-protected power, and heavy-rated casters (pneumatic tires on the Contractor Plus). Options include washable aluminum pre-filters, three-phase motors, discharge dampers, ducting kits, and suspension or through-the-wall mounting.
What we need to size your unit
You'll talk to the people who design and build the equipment — no dealer layers. The more of this you can tell us up front, the faster we can spec it.
- What you're cooling — a space, a process, or people.
- Approximate airflow or square footage of the area.
- Your location and climate — it drives how big a temperature drop to expect.
- Available power — single or three phase.
- Move or stay put — whether the unit needs to roll, hang, or mount through the wall.
Don't have all of it? Call anyway. Square footage and your city are usually enough for us to point you at the right model and a ballpark.
Not sure a portable is the right form factor at all? Stationary systems cover permanent installations, and specialty coolers exist for applications nothing off the shelf fits.
Not what you're looking for?
Stationary Systems
RTA series coolers from 9,000 CFM, retro-fit wet sections, and packaged units built to spec.
Condenser Pre-Coolers
Drop condenser intake air temperature, lower head pressure, and let your compressors work less for the same tonnage.
Replacement Media
Munters CELdek® rigid media in standard and cut-to-order sizes for the units you already run.
Which model fits your space?
Tell us the square footage, the heat load, and the power you have available. We'll size it and quote it straight from the factory.